Description
IP66 SUNIN-30KM3-H1P3 Hybrid Inverter
| Models | SUNIN-30KM3-H1P3-EU | SUNIN-40KM3-H1P3-EU | SUNIN-50KM4-H1P3-EU |
|---|---|---|---|
| Input DC (PV side) | |||
| Recommended max. PV array size | 60 kW | 80 kW | 100 kW |
| Max. usable PV input power | 60 kW | 80 kW | 96 kW |
| Max. input voltage | 1000 V | ||
| Rated voltage | 600 V | ||
| Start-up voltage | 180 V | ||
| MPPT voltage range | 150 – 850 V | ||
| Max. input current | 40 A / 40 A / 40 A | 4 × 40 A | 4 × 40 A |
| Max. short circuit current | 60 A / 60 A / 60 A | 4 × 60 A | 4 × 60 A |
| MPPT number / Max. input strings number | 3 / 6 | 4 / 8 | 4 / 8 |
| Battery | |||
| Battery type | Li-ion | ||
| Battery voltage range | 150 – 800 V | ||
| Max. charge / discharge power | 33 kW | 44 kW | 55 kW |
| Max. charge / discharge current | 70 A × 2 ① | ||
| Number of battery ports | 2 | ||
| Max. charge / discharge power of each input | 33 kW | 35 kW | 35 kW |
| Communication | CAN / Rs485 | ||
| Output AC (Grid side) | |||
| Rated output power | 30 kW | 40 kW | 50 kW |
| Max. apparent output power | 30 kVA | 40 kVA | 50 kVA |
| Rated grid voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | ||
| Rated grid frequency | 50 Hz / 60 Hz | ||
| Rated grid output current | 45.6 A / 43.3 A | 60.8 A / 57.7 A | 76 A / 72.2 A |
| Max. output current | 45.6 A / 43.3 A | 60.8 A / 57.7 A > < |
76 A / 72.2 A |
| Power factor | 0.99 (0.8 leading – 0.8 lagging) | ||
| THDi | 3% | ||
| Input AC (Grid side) | |||
| Max. AC passthrough current | 91.2 A / 86.6 A | 121.6A / 115.4 A | 152 A / 144.4 A |
| Rated input voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | ||
| Rated input frequency | 50 Hz / 60 Hz | ||
| Input Generator | |||
| Max. input power | 30 kW | 40 kW | 50 kW |
| Rated input current | 45.6 A / 43.3 A | 60.8 A / 57.7 A | 76 A / 72.2 A |
| Rated input voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | ||
| Rated input frequency | 50 Hz / 60 Hz | ||
| Output AC (Back-up) | |||
| Rated output power | 30 kW | 40 kW | 50 kW |
| Max. apparent output power | 1.6 times of rated power, 2 s < |
||
| Back-up switch time | 10 ms | ||
| Rated output voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | ||
| Rated frequency | 50 Hz / 60 Hz | ||
| Rated output current | 45.6 A / 43.3 A | 60.8 A / 57.7 A < |
76 A / 72.2 A |
| THDv (@linear load) | 2% | ||
| Efficiency | |||
| Max. efficiency | 97.8% | ||
| EU efficiency | 97.4% | ||
| BAT charged by PV max. efficiency | 98.5% | ||
| BAT charged / discharged to AC max. efficiency | 97.5% | ||
| Protection | |||
| Anti-islanding protection | Yes | ||
| Output over current protection | Yes | ||
| Short circuit protection | Yes | ||
| Integrated DC switch | Yes | ||
| DC reverse-polarity protection | Yes | ||
| Surge protection | DC Type II / AC Type II | ||
| Integrated AFCI 2.0 | Optional | ||
| General Data | |||
| Dimensions (W × H × D) | 530 × 880 × 290 mm | ||
| Weight | 73 kg | ||
| Topology | Transformerless < |
||
| Self-consumption (night) | 35 W | ||
| Operating ambient temperature range | -25 ~ +60°C | ||
| Relative humidity | 0 – 100% | ||
| Ingress protection | IP66 | ||
| Cooling concept | Intelligent fan-cooling | ||
| Max. operation altitude | 4000 m | ||
| Grid connection standard | G99, VDE-AR-N 4105/VDE V 0124, EN 50549-1/EN 50549-10, VDE 0126/UTE C 15/VFR:2019, NTS 631/ RD 1699/RD 244/UNE 206006/UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA,PORTARIA Nº 140, DE 21 DE MARÇO DE 2022 |
||
| Safety / EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4, EN 55011 | ||
| Features | |||
| PV connection | MC4 Quick connection plug | ||
| Battery connection | Terminal connector | ||
| AC connection | Terminal Block | ||
| Display | LED indicator & Bluetooth + APP | ||
| Communication | CAN, RS485, Ethernet, Optional: Wi-Fi, Cellular, LA | ||






Avis